Danfoss AK-SM 800A: reported unpatched pre-auth remote code execution flaws; earlier flaws fixed in 4.3.1

Danfoss AK-SM 800 / StoreView · CriticalFix available

Published 14/11/2026 09:15

Timeline

2 events over 1 d 21 h

  1. 12/11/2026 11:59UnconfirmedCommunity post+1 d 21 h
  2. 14/11/2026 09:15Published on WatchtowerPro CISO

In short

A researcher reportedly found at least five new pre-auth remote code execution flaws in Danfoss AK-SM 800A refrigeration controllers that are still unpatched. Earlier flaws are fixed in 4.3.1. Until a patch is available, remove internet exposure and allow access only through a VPN.

How bad is it

High. An attacker who reaches a vulnerable controller's web interface can bypass the login, and with a login can run commands on the device or disrupt it.

No exploitation reported yet.

Severity score

No CVSS score published yet

A missing score is never read as 0.

What an attacker needs

  • Internet access to itNot published yet
  • A loginNot published yet
  • A user to clickNot published yet
  • Special settingsNot published yet

Red helps the attacker, blue holds them back, grey is not published yet.

A score is the worst case for the flaw, not a verdict on any one system. How we score · ReconX customers see which of their own systems are affected.

Affected versions

  • AK-SM 8xxA versions prior to R4.2 are affected by CVE-2025-41450, a password generated from the date and time.
  • AK-SM 8xxA Series prior to version 4.3.1 are affected by CVE-2025-41451 and CVE-2025-41452 (post-authentication).

Fixed in

  • 4.3 branch: 4.3.1 (released 01/08/2025 00:00 Amsterdam time)

What to do now

  • Update AK-SM 800A units to at least 4.3.1, which fixes CVE-2025-41451 and CVE-2025-41452 and also covers the R4.2 fix for CVE-2025-41450.
  • Interim measures reduce exposure and do not make a controller safe; they do not replace updating.
  • Remove direct internet exposure and allow remote access only through a VPN behind a deny-by-default stateful firewall.
  • Change the factory user and password, and set Configuration > Security-Strict.
  • Plan to replace AK-SM 800 and AK-SC355 units, which are out of service.

ReconX customers see the full notice - and their own systems

Our customers are alerted at every phase. Until a patch exists, the ReconX agent watches their servers from the inside for anomalies, and our outside view - the attacker's view - shows which systems to fix first.

In ReconX: the full analysis, 5 open questions, followed up as sources answer and all 5 sources with their dates. And technology matching: which of your systems run Danfoss AK-SM 800 / StoreView, at which version, fixed or not - and what each one needs.

Sign in to ReconXAbout ReconX

Main sources

DSA-2025-03-01 Research · Danfoss AK-SM 8xxA Series (Update A) Research · DSA-2025-08-01 Research

← All Watchtower notices

Pro CISO publishes ReconX Watchtower notices from public sources so organisations can act early. A notice describes an issue, never any organisation's systems. Times are Amsterdam time. Report a vulnerability in our systems.

ReconX Watchtower opened to the public on 24 October 2026, in the wake of PHP2Shell - our contribution to a safer digital ecosystem.